9 min readupdated

Firefighters preparing equipment in the open lockers of a fire engineFot. Marianna Zuzanna

In Poland, there is no regulation that says outright how to protect a garage with chargers. There are general requirements for garages and electrical installations, a few sentences in the Electromobility Act and extensive expert guidelines that are not law. The gap is filled by a certified fire-safety expert — and it is their assessment that decides whether linking the chargers to the fire-fighter’s power cut-off switch is enough in a garage, or whether detection above the charging bays will be needed. We set out what is an obligation, what is a recommendation and how experts approach the matter at the end of 2026.

Where the requirements come from: a map of the regulations

Fire-safety requirements for chargers in a building do not come from a single act. They are made up of building regulations, fire protection regulations and a few provisions on the charging stations themselves:

  • The Fire Protection Act — the duties of the owner and, to the extent taken over under a contract, also of the property manager (Article 4), alternative solutions to which the regional commander of the State Fire Service (PSP) gives consent (Article 6a), and design approval by a fire-safety expert (Article 6b).
  • The technical building regulations — requirements for garages: division into fire zones, smoke extraction, escape exits, fixed fire-extinguishing systems in deep underground garages and a fire-fighter’s power cut-off switch (PWP) in fire zones with a volume exceeding 1,000 m³ (§ 183(2) of the 2002 regulation).
  • The Interior Ministry regulation on fire protection of buildings — fire extinguishers, inspections and maintenance of fire protection equipment at least once a year, and fire safety instructions, required among other things for a garage fire zone with a volume above 1,000 m³ and updated after changes affecting fire protection conditions.
  • The Electromobility Act — the feasibility assessment for a charging point in a multi-family building with more than three flats must set out fire-safety requirements (Article 12c(5), point 5), and charging stations must meet the requirements of Polish Standards, including those on fire safety (Article 13).
  • The regulation on technical requirements for charging stations and charging points — protection against vehicle impact (§ 8), a ban on extension cords (§ 10), a description of what to do in the event of a fire in the operating instructions (§ 22) and, for a station subject to UDT inspection, a fire-safety expert’s opinion attached to the application for the initial inspection (§ 20, point 9).

What the regulations still lack

None of these acts says how many chargers can be installed in a garage, how far from the exits they must be, or whether a detector is required above a charging bay. Nor do the regulations ban parking electric cars in underground garages — bans, where they appear, come from property managers’ decisions, not from the law.

The new technical building regulations do not change this. The 2002 regulation was in force until 19 September 2026, but for 18 months from 20 September 2026 an investor may — after submitting a declaration — continue to apply it to the design and construction works (Articles 102a and 102b of the Building Law). The draft of the new regulation (version of 24 April 2026) repeats the existing rules in its chapter on garages — fire zones, smoke extraction where there is no direct vehicle access or the fire zone area exceeds 1,500 m², fixed fire-extinguishing systems in garages spanning more than two underground levels or located below the second underground level — and contains no provisions on charging points. It does, however, regulate battery energy storage systems (BESS) in detail, which was previously missing. According to reports of 20 November 2026, the regulation has been signed; as of 24 November it had not been published in the Journal of Laws, so the final text may differ from the draft.

In practice, therefore, the protection of a garage with chargers is decided by an assessment of the specific building based on the principles of current technical knowledge. Fire-safety experts and designers treat the CNBOP-PIB guidelines as the reference point for those principles.

CNBOP-PIB, KG PSP and PSNM guidelines: the reference point

The guidelines on fire protection of garages intended for charging electric and plug-in hybrid vehicles were prepared by CNBOP-PIB (the Polish Scientific and Research Centre for Fire Protection), the National Headquarters of the State Fire Service (KG PSP) and the Polish Association of New Mobility (PSNM). The first edition was published in 2024, and the second — updated to include, among other things, requirements for surge protection of charging points — in May 2025. The guidelines describe themselves as a set of requirements and recommendations, but they are not legislation — they are a document that fire-safety experts and designers use as a reference point.

The core of the guidelines is two goals: detect a fire quickly and limit its spread, at least until the fire service arrives. According to overviews of the guidelines, the main recommendations follow from this:

  • Fast detection: the guidelines consider it unacceptable to install charging points in a garage without measures for fast fire detection and for passing the information to the State Fire Service or to people who will alert it immediately (e.g. security staff). It does not have to be a classic fire alarm system — video-based detection or wireless detectors with the appropriate approval documents, for example, are also acceptable.
  • Limiting fire spread: fixed fire-extinguishing systems or passive protection — e.g. walls with a fire resistance class of at least EI 30 or E 60 and a height of at least 1.8 m, or other separations effective for at least 30 minutes. Where fixed fire-extinguishing systems are installed, passive protection is not required, and whether to use it depends on the building’s circumstances.
  • The ability to quickly disconnect power to the chargers — where the building has no PWP, a dedicated charging station switch is considered.
  • Preparing the building for rescue operations (vehicle access, access to the charging bays, evacuation conditions) and a correctly made electrical installation with overcurrent, residual current and surge protection.
  • Additional protection is justified, among other things, with a high concentration of charging points, places that are hard for the fire service to reach, fire-unit response times longer than 15 minutes and detection other than a fire alarm system. A more lenient approach is provided for garages in residential buildings if, among other things, all charging bays have detection with fire-service notification, the garage has a clear height of at least 2.7 m and the fire service response time does not exceed 15 minutes.

How fire-safety experts approach it today

A similar approach recurs in fire-safety experts’ publications and in opinions for garages: a risk assessment of the specific garage, with the CNBOP-PIB guidelines as the reference point. The expert starts from what the building already has — division into fire zones, escape routes, existing fire protection equipment — and only then selects additional measures. A few elements often recur in their opinions:

  • Site analysis: the size and number of fire zones, underground levels, direct vehicle access, an existing fire alarm system, smoke extraction and sprinklers, fire-service access, and the target — not just the initial — number of charging points.
  • Disconnecting the chargers: a link to the PWP and, in garages with a fire alarm system, automatic cut-off of the chargers’ power supply after an alarm. This is one of the most common recommendations.
  • Detection above the charging bays where the garage has no fire alarm system — treated, in line with the guidelines, as a condition rather than an add-on.
  • Location and grouping: usually points close to the entrance, away from escape routes, with protection against vehicle impact, plus signage for charging bays and switches.
  • Measures limiting fire spread (separations, fixed fire-extinguishing systems) — usually only with many charging points, in hard-to-reach parts of the garage or on lower underground levels.
  • Documents: an update of the fire safety instructions (mandatory where the building must have them) and — for stations subject to UDT — the opinion for the initial inspection application.

Why opinions from different experts differ

Since the regulations do not set the requirements outright, two similar garages can receive different opinions: from “PWP, signage and an update of the instructions” to “detection throughout the garage and separations between groups of bays”. Representatives of the institutions that prepared the guidelines pointed to such discrepancies after site inspections of Warsaw garages in 2023: those responsible for fire protection assessed the hazards of electric cars differently, and solutions were often sought only once the building was already in use.

Two roles of the expert also need to be distinguished. Agreeing a design means confirming its compliance with fire protection requirements (Article 6b of the Act), so comments in the approval should stem from those requirements — the mere presence of chargers does not create an obligation to install equipment that the regulations do not require for the garage. In an opinion, however, the expert can recommend measures beyond the minimum, and whether to apply them is up to the investor or property manager. It is different with an alternative solution to which the regional commander of the State Fire Service has given consent — including on condition that additional requirements are met (Article 6a): it then replaces a legal requirement and must be implemented.

For a housing community board, the practical conclusion is simple: for every recommendation, it is worth asking whether it comes from a regulation, from the guidelines or from the building’s risk assessment — and what cheaper solutions would have a similar effect.

Assessment, opinion, design approval: who is responsible for what

  • Feasibility assessment (Article 12c of the Electromobility Act) — for a resident’s charger in a multi-family building with more than three flats. It is prepared by a person holding unrestricted building design qualifications in the electrical installations speciality. Among other things, it must set out the power available for the charging point and the fire-safety requirements — in enclosed garages, in practice, it relies on the assessment of a certified fire-safety expert.
  • Opinion of a certified fire-safety expert — assesses the impact of the charging installation on the building’s fire safety and indicates the protection needed. It is a mandatory attachment to the application for an initial UDT inspection of a charging station (§ 20, point 9 of the charging station regulation).
  • Design approval by a fire-safety expert (Article 6b of the Fire Protection Act) — required for the design of fire protection equipment, e.g. extending the fire alarm system to control the chargers, and for the design of the reconstruction of a building listed in the 2023 Interior Ministry regulation — including a multi-storey garage or an enclosed garage with smoke extraction or sprinklers — if the design concerns fire protection conditions.
  • Day-to-day responsibility for the garage’s fire safety — the owner and, to the extent transferred under a contract, the property manager (Article 4 of the Act): inspections of fire protection equipment at least once a year, up-to-date fire safety instructions, clear access routes.

Typical recommendations depending on the garage

  • A garage with a fire alarm system and smoke extraction: automatic disconnection of the chargers after an alarm, a check that the detectors cover the charging bays, the location of the points, signage and an update of the instructions.
  • A small single-level garage with direct vehicle access and no fire alarm system: disconnection via the PWP or a dedicated charger switch at the entrance, local detection above the charging bays with notification, points close to the entrance.
  • A large or multi-level garage with many charging points: in addition, grouping of the points, an assessment of existing sprinklers or passive protection, and planning for the target number of chargers rather than the first few.
  • An outdoor car park or open garage: usually the fewest requirements — protection against vehicle impact, an emergency switch at DC stations, signage.

We describe practice, not the requirements for a specific building. The scope of protection is determined by a fire-safety expert after analysing the building; this article does not replace a fire-safety opinion.

How to prepare for the fire-safety expert’s opinion

  • Gather the documents: the building design or an as-built survey of the garage, the fire safety instructions, inspection reports for the fire alarm system, smoke extraction and PWP, and the switchboard diagram.
  • Set the target scale: how many residents or tenants may want to charge within a few years. One opinion for the whole garage is cheaper and more consistent than several opinions for individual chargers.
  • Combine the fire-safety analysis with the power analysis: load management (DLB) lets you fit more points on the existing connection, and the layout of the points affects both assessments at once.
  • Ask for the recommendations to be justified and classified: an obligation under the regulations, an alternative solution, or a recommendation beyond the minimum.

Calculate the cost of your documentation

Enter the number of charging points and we will calculate the net and gross amount incl. 23% VAT.

Additional points within a single documentation set are cheaper: the first point is the full assessment, and each further one is only +300 zł net — the more points, the lower the cost per point.

Number of charging points

We price the assessment and design per point; fire-safety sign-off once per building.

1
Documentation scope
Assessment2 500 zł netto
VAT 23%575 zł
Razem brutto3 075 zł z VAT 23%
Book an assessment

* Applies to connection to the building’s existing distribution board, provided the full required electrical documentation and floor plans are supplied.

Frequently asked questions

  • No. General requirements for garages and electrical installations apply, and the Electromobility Act requires the feasibility assessment to set out fire-safety requirements. The details are determined by a fire-safety expert, usually based on the CNBOP-PIB guidelines. The draft of the new technical building regulations contains no provisions on charging points either.

Related services

We handle the entire process turnkey — see how we can help:

Sources

Read also

Have a question about charging at your property?

Let’s talk

Let’s talk about working together

Call or write — we’ll answer your questions about assessment, installation and charger billing. You can also leave an enquiry in the form beside this.

Office

Working days, 8:00–18:00

Technical support

Every day, 8:00–22:00

I am interested in:

You can select several options.

Provide it if you are enquiring on behalf of a housing community or company. Individual clients can leave it blank.

Leave a number if you prefer a call. Otherwise we will reply by e-mail.

Helps us plan the travel to your site.

Tell us about the project: type of property, number of charging points, location. It helps us prepare a quote.